About REC Temovex RT-400S-EC-RS
EC Temovex 400S-EC-RS is an air handling unit (AHU) designed for highly efficient ventilation and heat recovery. It is designed as a part of the white goods, and ready to be installed on the floor in a bathroom, boiler room, laundry or similar.
RT400S-EC-RS consists of fans, filters, after-heater (electric or water), automatic by-pass, integrated control panel and a counter-flow heat exchanger.
The casing is made of double hot galvanised sheet metal with 30 mm insulation between the sheets. The front and the side panels are white (RAL 9016, powder painted) and the front door has a magnetic strip to keep it closed.
Our counter-flow heat exchanger makes it possible to utilize the thermal energy in the used indoor air and use it to heat the fresh incoming air. The counter-flow heat exchanger also ensures that there is no leakage between used air and fresh air. As a result, you get a good operating economy and a sound and comfortable indoor climate.
Certifications
Documents
| After-heater – Electrical |
|
| Rated output, unit | 1138 W |
| Rated output, standard heater | 900 W |
| Rated output, reinforced heater | 1800 W |
| Rated output, fans | 2 x 119 W |
| Voltage/Frequency input | 230 V, 50 Hz |
| Fuse | 10 A |
| Filter, supply air / exhaust air | Bag ePM1 50%/Bag Coarse 60% |
| Weight | 100 kg |
| Water connection | – |
| Fire classification | A15 |
| Measurements (WxDxH) | 430x620x1900 mm |
| Duct connections | 4 x Ø160 mm |
| Condensate drain | 3/4” |
| After-heater – HW Water temp. 55/45°C |
|
| Rated output, unit | 238 W |
| Rated output, standard heater | 1500 W at 85 l/s |
| Rated output, reinforced heater | 2800 W at 85 l/s |
| Rated output, fans | 2 x 119 W |
| Voltage/Frequency input | 230 V, 50 Hz |
| Fuse | 10 A |
| Filter, supply air / exhaust air | Bag ePM1 50%/Bag Coarse 60% |
| Weight | 100 kg |
| Water connection | DN12 |
| Fire classification | A15 |
| Measurements (WxDxH) | 430x620x1900 mm |
| Duct connections | 4 x Ø160 mm |
| Condensate drain | 3/4” |
| OPTIONS in addition to standard execution | Name |
| After-heater battery electrical (reinforced) 1,8 kW, built-in | EVB1,8 |
| After-heater water coil, built in(incl. 2 way valve and 0-10V actuator) | EVBV |
| After-heater water coil (reinforced), built-in (incl. 2 way valve and 0-10V actuator) | EVBV2 |
| Cooling coil, external (incl. 2 way valve and 0-10V actuator) | EKB |
| Cooling coil (reinforced), external (incl. 2 way valve and 0-10V actuator) | EKB2 |
| Condensation boiler, built-in | KAVK |
| Outdoor air damper with spring return | SPM160 |
| ECO2 Control system for air heating | ECO2 |
| Fireplace compensation incl. timer and switch | BRAS |
| Protection class IPX5 | IPX5 |
| Modbus or EXOline (RS485) | KOM |
| Remote panel (with or without display) | Fjärr |
| Web connection (cost of subscription excluded) | REC Live |
| Top cover for lining | Topp |
| Fire function | BRAND |